Eaton PPF1003CEI, DEI and EEI Technical Specifications

Eaton PPF1003CEI, DEI and EEI
General
Dimensions (H x W x D, mm) 800 x 600 x 200
Weight (kg) 50
Warranty 5 years
 
Electrical
Input voltage 380 - 440VAC 3 Phase
Max Continuous Voltage (Mcov) 300VAC L-N
Temporary overvoltage - TOV 320VAC, 15 mins
Service type TT, TN, TN C-S or any 3-phase system with a grounded neutral.
This unit must not be connected to an ungrounded system
Test classification Class II
Energy Absorption rating - per mode (Joules)

Primary protection L-N:
Secondary protection L-N:
Common mode protection N-E:
Aggregate rating:



CEi: 1,200J/ph, 3,600J total. DEi: 1,800J/ph, 5400J total. EEi: 3,600J/ph, 10,8000J total.
CEi: 600J/ph, 1,600J total. DEi: 600J/ph, 1,800J total. EEi: 600J/ph, 1,800J total.
CEi: 2,130J. DEi: 710J. EEi: 710J
CEi: 7,530J. DEi: 7,910J.. EEi: 13,310J.
Current rating – continuous (standard models) 100A
Recommended maximum over current protection 100A
Residual current <1 mA
Short circuit withstand (1 sec) 29kA
Protection modes Line-Neutral, Neutral-Earth
In 8/20us (Line-Neutral) Nominal Surge Life CEi: 30kA x 20 hits/ph; DEi: 45kA x 20 hits/ph; EEI: 90kA x 20 hits/ph
In 8/20us (Neutral-Earth) Nominal Surge Life 45kA x 20 hits
Ismax 8/20us (Line-Neutral) Max surge level CEi: 80kA; DEi: 120kA; EEI: 240kA
Ismax 8/20us (Neutral-Earth) Max surge level CEi: 120kA; DEi: 40kA; EEI: 40kA
Filter attenuation 70dB nominal above 1MHz
Initial clamp voltage (Line-Neutral) 560V (350Vac RMS)
Initial clamp voltage (Line-Earth) 1240V (700Vac RMS)
Initial clamp voltage (Neutral-Earth) 680V (420Vac RMS)
Residual voltage (Vpl) Line-Neutral <900Vac (3kA, 8/20uS) IEC61643.1
Residual voltage (Vpl) Line-Earth <1100Vac (3kA, 8/20uS) IEC61643.1
Residual voltage (Vpl) Neutral-Earth <1000Vac (3kA, 8/20uS) IEC61643.1
Internal protection (fusing) All surge diverter connections are fused via HRC fuses to IEC269-2-1
Terminations Bolted lug. 8mm bolts for phase & neutral connections. 8mm PE (earth) stud provided on geartray.
 
Communications
Alarms/indicators Mimic panel display via LED (2 colour), OK - Green; Protection Fault - Red. Dry contact alarm relay output – 250Vac/32Vdc, 10A, 4kV isolation, Alarm under-voltage cutoff 180Vac
Environmental & Standards
Enclosure rating IP24
Design standards IEC61643-1, IEC610006-1,2,3,4 ANSI/IEEE C62.41 Cat B,C,D AS1768-2007 Cat B,C,D,E AS3000, AS3100, CE mark
Environment -10 to 65°C, 10 to 90%RH (non-condensing)
   
Notes
Due to continual product improvement specifications are subject to change without notice