Eaton PPF1003D-GT Technical Specifications

Eaton PPF1003D-GT
General
Dimensions (H x W x D, mm) 500 x 400 x 200
Weight (kg) 20
Warranty 5 years, workmanship and materials
Installation instructions Supplied with unit
Location Category Indoor
Mounting points (4x) 9mm holes, centres 460H x 360W (mm)
 
Electrical
Number of ports 2 Port series connected
Number of phases 3 phase, Neutral & Earth
Method of mounting Gear tray
Input voltage 380-4400v 3 ph
Max Continuous Voltage (Mcov) 320VAC L-N per phase
Temporary overvoltage - TOV 350VAC L-N, 15 mins per phase
Service type TT, TN, TN C-S or any 3-phase system with a grounded neutral.
This unit must not be connected to an ungrounded system
Test classification Class II
Energy Absorption rating - per mode (Joules)

Primary protection L-N:
Secondary protection L-N:
Common mode protection N-E:
Aggregate rating:



2130 J/ph, 6390 J total
710J/ph, 2130 J total
710 J
9230 J
Current rating – continuous 200A
Recommended maximum over current protection Match to current rating of unit.
Residual current <1 mA
Short circuit withstand (1 sec) 29kA
Protection modes Line-Neutral, Neutral-Earth
In 8/20us (Line-Neutral) Nominal Surge Life 45kA
In 8/20us (Neutral-Earth) Nominal Surge Life 45kA
Ismax 8/20us (Line-Neutral) Max surge level 100kA
Ismax 8/20us (Neutral-Earth) Max surge level 50kA
Filter attenuation > 65dB nominal above 1MHz
   
Initial clamp voltage (Line-Neutral) 560V
Initial clamp voltage (Neutral-Earth) 680V
Residual voltage (Vpl) (Line-Neutral). (Let through voltage) <1000Vac (3kA, 8/20uS)
Residual voltage (Vpl) (Neutral- Earth). (Let through voltage) <1100Vac (3kA, 8/20uS)
Internal protection (fusing) All surge diverter elements are thermally fused
External disconnector requirement
Line side:
Load side:

3 pole, HRC or GL fuse, 500v, >50KAIC max 100A & 200A
3 pole, 100A & 200A MCB
Terminations Bolted lug. 8mm bolts for phase and neutral connections. 8mm PE (earth) stud provided on gear tray. All connections identified on unit.
 
Communications
Alarms/indicators Each internal SPD includes status indictors. Blue led for each surge diverter for OK. Red led each diverter for protection failure. Dry contact alarm rely output ( normally closed with power applied and all diverters at 100% capacity ). Dry contact alarm relay output – Rating: 250Vac/32Vdc, 5A, 4kV isolation. Alarm under-voltage cut-off at 180Vac.
Environmental & Standards
Enclosure rating IP24
Design standards IEC61643-1, IEC610006-1,2,3,4 ANSI/IEEE C62.41 Cat B,C,D AS1768-1991 Cat B,C,D, AS3000,AS3100, CE mark
Environment -10 to 65°C, 10 to 90%RH (non-condensing)
Thermal dissipation 100W for 100A, 150W for 200A @ full load
   
Notes
1. Installation must be carried out by suitably qualified personnel. Please refer to installation instructions for details.
2. Due to continual product improvement specifications are subject to change without notice.