Eaton PPF6003CEI, DEI and EEI Technical Specifications

Eaton PPF6003CEI, DEI and EEI
General
Dimensions excluding vertical mounting rails (H x W x D, mm) 1200 x 800 x 310
Weight (kg) 100
Warranty 5 years, workmanship and materials
Installation instructions Supplied with unit
 
Electrical
Number of ports 2 Port
Method of mounting Fixed, side mounting rail
Input voltage 380-4400v 3 ph
Max Continuous Voltage (Mcov) 300v L-N
Temporary overvoltage - TOV 320VAC L-N, 15 mins
Service type TT, TN, TN C-S or any 3-phase system with a grounded neutral.
Test classification Class II
Energy Absorption rating - per mode (Joules)

Primary protection L-N:
Secondary protection L-N:
Common mode protection N-E:



CEi: 1200J ph. DEi: 1,800J ph. EEi: 3,600J ph.
CEi: 600J ph. DEi: 600J ph. EEi: 600J ph.
CEi: 2,130J. DEi: 710J. EEi: 710J
Current rating – continuous (standard models) 600A
Recommended maximum over current protection 600A
Residual current <1 mA
Protection modes Line-Neutral, Neutral-Earth
In 8/20us (Line-Neutral) Nominal Surge Life CEi: 30kA x 20 hits/ph; DEi: 45kA x 20 hits/ph; EEI: 90kA x 20 hits/ph
In 8/20us (Neutral-Earth) Nominal Surge Life 45kA x 20 hits
Imax 8/20us (Line-Neutral) Max surge level CEi: 80kA x 1 hits/ph; DEi: 100kA x 1 hits/ph; EEI: 240kA x 1 hits/ph
Imax 8/20us (Neutral-Earth) Max surge level CEi: 100kA x 1 hits; DEi: 40kA x 1 hits; EEI: 40kA x 1 hits
Noise filtering Up to -72dB above 1MHz Line, Up to -70dB above 1MHz Neutral
Noise rejection @ cut off frequency ( full load ) -7dB @ 1KHz
Initial clamp voltage (Line-Neutral) 560V
Initial clamp voltage (Neutral-Earth) 680V
Residual voltage (Vpl) (Line-Neutral). (Let through voltage) <900v (3kA, 8/20uS) IEC61643.1
<700v ( 3kA, 8/20us, UL1449 )
Residual voltage (Vpl) (Neutral- Earth). (Let through voltage) <1100Vac (3kA, 8/20uS) IEC61643.1
Safety disconnect Thermal fusing on MOV’s, HRC fusing on each surge diverter
External disconnector requirement 600A and 800A 6KAIC MCB
Terminations 2 x 12mm bolt to busbar per phase and Neutral. M12 bolt to Earth
 
Communications
Alarms/indicators Full mimic display panel via leds. Green = OK. Red = Protection Fault. Dry contact alarm relay output. Alarm under-voltage cut off 180VAC.
Environmental & Standards
Enclosure rating IP24
Design standards IEC61643-1, IEC610006- 1,2,3,4, ANSI/IEEE C62.41 Cat C & B, AS1768-2007 Cat C & B, AS3000 AS3100, CE mark
Environment -10 to 60°C, 0 to 95%RH (non-condensing)
   
Notes
Due to continual product improvement specifications are subject to change without notice