Eaton SPDV60-300 Technical Specifications

Eaton SPDV60-300
General
Dimensions (not incl relay) 17 x 68 x 90
Weight (g) 100
 
Electrical
Input voltage 220-250VAC (380-480V)
40-70 Hz
Maximum continuous operating voltage (MCOV) 300VAC
Shunt Technology MOV
Service Type TN-C & TN C-S (3-Phase with grounded neutral)
Test Classification (IEC61643-1) Class II
Initial clamp voltage 470V
Initial spark over voltage N/A
Maximum rated surge current - Ismax 8/20us 60kA
Nominal surge current - In 8/20us 30kA
Residual voltage (Vpl) @ 3kA, 8/20us 1.0kV
Residual voltage (Vpl) @ Ismax, 8/20us 1.4kV  
Energy absorption (2ms) 2130 Joules
Nominal surge lifetime (In) 30kA (8/20us), 20 times
Internal protection MOV thermal disconnect device
Recommended maximum over-current protection gG/gL HRC fuses, 1 per phase, 160A maximum
Terminations Power terminals 16mm², Alarm terminals 1.5mm²
Supply Current<10mA
 
Communications
Alarms/indicatorsFlag indicator, dry contact alarm relay - 250VAC/24VDC, 2A
   
Environmental & Standards
Design standards IEC61643-1, IEC610006, ANSI/IEEE C62.41, AS1768-2007, AS3100, CE mark
   
Notes